The Ames ATG-1 Backflow Preventer Test
Kit is a compact portable testing device
made for testing all Reduced Pressure
Zone Backflow Prevention Assemblies and
Double Check Valve Assemblies. The ATG-1
is easily connected to any RPZ device
enabling accurate testing of ‘zone’ differential
pressure, relief valve opening differential,
fouled check valves or similar problems that
visual inspections cannot locate. The unit is
supplied with a rugged carrying case for easy
handling and accessibility.
Specifications
• Maximumworkingpressure–175psi
(12.1bar)
• Maximumworkingtemperature–210°F
• Gauge–4
1
2”diameterfacedualscale
0–15psiand0–1kg/cm
2
,±2%
accuracyfullscale
• TestValves–(2)ballvalvesand
(1)needlevalve
• Hoses–(3)3’withfemalethreaded
swivelcouplings
• Adaptors–(3)
1
4”threadedcoupling
adaptors
(3)
1
2”x
1
4”bushings
(3)
3
4”x
1
4”bushings
• 1–16”securingstrap
• 1–Moistureresistantinstructionguide
• Case–lightweight,shockresistantmolded
plasticwithfoaminserts
Series ATG-1
Limited Warranty: Ames Fire & Waterworks (the “Company”) warrants each product to be free from defects in material and
workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within
the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH
RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY
SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty,
and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost
profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs
resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water
conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by
any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation
of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you
specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT
BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE,
ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
www.amesfirewater.com
A Watts Water Technologies Company
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Series ATG-1

IS-A-ATG-1Backflow Preventer Test KitThe Ames ATG-1 Backflow Preventer Test Kit is a compact portable testing device made for testing all Reduced Pre

Page 2

2Reduced Pressure Zone Assemblies must be inspected and tested periodically, in accordance with local codes, to ensure proper operation of check valve

Page 3

31. When using differential pressure gaugeA.CheckdifferentialacrossNo.1checkvalveReading Problem 2to3PSID LeakinNo.1orNo.2checkvalv

Page 4 - Test for Leaky No. 2 Shutoff

Test Check Valve No. 1Step 1: Ensure shutoff #1 is open, shutoff #2 is closed.Step 2: Connect high side hose to test cock #3, low side to test cock